- Product Type: Multi-MPPT String Inverter.
- Power Capacity: 110 kVA @ 45°C, 100 kVA @ 50°C.
- Input (DC):
- Max. PV input voltage: 1100 V.
- Min. PV input voltage: 200 V.
- Startup input voltage: 250 V.
- Nominal PV input voltage: 585 V.
- MPP voltage range: 200 – 1000 V.
- MPP voltage range for nominal power: 550 – 850 V.
- Number of independent MPP inputs: 9.
- Max. number of PV strings per MPPT: 2.
- Max. PV input current: 26 A * 9.
- Max. DC short-circuit current: 40 A * 9.
- Output (AC):
- Nominal AC output power: 110 kVA.
- Max. AC output current: 158.8 A.
- Nominal AC voltage: 400 V.
- AC voltage range: 320 – 460 V.
- Nominal grid frequency: 50 Hz / 60 Hz.
- Grid frequency range: 45 – 65 Hz.
- Total Harmonic Distortion (THD): < 3% (at nominal power).
- DC current injection: < 0.5% In.
- Power factor: > 0.99 / 0.8 leading – 0.8 lagging.
- Feed-in phases: 3 / N / PE.
- Efficiency:
- Max. efficiency: 98.7%.
- European efficiency: 98.5%.
- Protection Features:
- DC reverse connection protection.
- AC short circuit protection.
- Leakage current protection.
- Grid monitoring.
- Ground fault monitoring.
- Overvoltage protection (DC Type II / AC Type II).
- PV String current monitoring.
- PID recovery function.
- DC switch and AC switch (not available for Australia).
- General Data:
- Dimensions (W x H x D): 1051 x 660 x 362.5 mm.
- Weight: 89 kg.
- Isolation method: Transformerless.
- Ingress protection rating: IP66.
- Night power consumption: < 2W.
- Operating ambient temperature range: -30 to 60°C (derating above 50°C).
- Allowable relative humidity range: 0 – 100%.
- Cooling method: Smart forced air cooling.
- Max. operating altitude: 4000 m (derating above 3000 m).
- Display: LED, Bluetooth + APP.
- Communication: RS485 / Optional: Wi-Fi, Ethernet.
- DC connection type: MC4 (Max. 6 mm²).
- AC connection type: OT / DT terminal (Max. 240 mm²).
- Grid Support Functions:
- Q at night function.
- LVRT, HVRT, active & reactive power control, and power ramp rate control.
- Certifications and Compliance:
- IEC 62109, IEC 61727, IEC 62116, IEC 60068, IEC 61683.
- VDE-AR-N 4110:2018, VDE-AR-N 4120:2018, EN 50549.
- AS/NZS 4777.2:2015, CEI 0-21, VDE 0126-1-1/A1, UTE C15-712-1:2013, DEWA.